We ship worldwide — Singapore, Australia, Malaysia, Indonesia, Philippines, India, Middle East & more

Beckett: GeniSys® 7590 24V Gas Burner Control - Controls

Complete Solution

Need installation, maintenance, or a bundled quote?
Our engineers can help with product selection, system design, installation, and ongoing service — all from one partner.

Quick Inquiry

BeckettControls
Available

Beckett: GeniSys® 7590 24V Gas Burner Control

SKU 3G-BKT-00044

Brand
Beckett
Item
: GeniSys® 7590 24V Gas Burner Control
Category
Controls
UNSPSC
39121026 — Control power transformer

Technical Specifications

Beckett
Models
7590D0001, 7590T0001, 7590C0001
Moisture
5 to 95% RH, non-condensing
Approvals
UL listing per ANSI Z21.20, UL372 and CSA C22.2 No. 199
Input Voltage
120 V, 50/60 Hz (igniter, motor); 24 V (18-30 VAC) 50/60 Hz (gas valve and air proving switch)
Ignition Timing
4-15 seconds
Pre-purge Timing
1-240 seconds
Main Valve Rating
2.0 amps
Current Draw (run)
0.2 amps (control only)
Inter-purge Timing
90-300 seconds
Motor Relay Rating
7.4 amps (120 V)
Thermostat Voltage
24 Vac (if used)
Igniter Relay Rating
1.0 amp (120 V)
Flame Detection Method
Flame rectification principles
Heat Anticipator Setting
0.2 amps + gas valve current draw
Flame Failure Response Time
0.8 seconds (maximum)
Minimum Flame Current Required
1.0 µA
Storage & Operating Ambient Temperature
-40°F to +175°F (-40°C to +79.4°C)
View Full Spec Sheet
Worldwide Shipping
Air & sea freight
Datasheet on Request
Technical specs
1-Day Quote
SG-based team
Sign in to view pricing
Create a free account to submit your RFQ and download technical documents.

Solutions Engineering

Need guidance on product selection or system design?
Contact Our Engineering Team
Beckett Products
3G Electric (S) Pte. Ltd. — Singapore

Product Description

24V safety control for gas burners in residential and light commercial heating systems, with flame rectification monitoring and diagnostic LEDs.

Key Features

  • Flame rectification technology for reliable flame detection
  • Supervises 120V igniter and combustion blower separately
  • 24V gas valve and air proving switch control (models 7590C/D)
  • 3 LED indicators for quick diagnostic status checks
  • Adjustable ignition timing from 4-15 seconds
  • Pre-purge duration selectable from 1-240 seconds
  • Configurable single or multiple ignition trial sequences
  • Microprocessor self-check prior to each operating cycle
  • Gas valve relay verification on every cycle
  • Available with manual reset and non-volatile lockout options
  • Suitable for natural gas or LP gas applications
  • Designed for 4x4 junction box mounting
  • Compatible with BeckettLink 7700A diagnostic tool

Used in

Common applications for Beckett
American-spec food-processing boiler burners — AFG scheduled-maintenance parts
Institutional kitchen and cafeteria plant — SF series for 3–7 GPH continuous duty
Commercial gas / dual-fuel — CG10 / CG15 / CG25 for medium-scale installations
Marine and offshore auxiliary plant — Beckett semi-commercial oil burners
Retrofit swap from ageing Italian burners where customer prefers American-style simpler service catalog

Beckett Products

3G Electric supplies Beckett controls. We supply genuine products with in-stock availability on common SKUs, technical documentation, commissioning support, and warranty service — worldwide.

You might also need

Burners & Combustion Pumps & Compressors Spare Parts All Products

More from BECKETT

View all BECKETT parts
Beckett: GeniSys® 7556 12V Oil Burner Control
BECKETT
Beckett: GeniSys® 7556 12V Oil Burner Control
Beckett: Replacement Cad Cell Eyes - 6 pack | 596101BU
BECKETT
Beckett: Replacement Cad Cell Eyes - 6 pack | 596101BU
Beckett: GeniSys® 7580 240V Oil Burner Control
BECKETT
Beckett: GeniSys® 7580 240V Oil Burner Control
Beckett: AquaSmart® Temperature Sensor | 7600TSU
BECKETT
Beckett: AquaSmart® Temperature Sensor | 7600TSU
Beckett: AquaSmart® Temperature Sensor with Water Level Detection | 7600P
BECKETT
Beckett: AquaSmart® Temperature Sensor with Water Level Detection | 7600P
Beckett: A/C Ready Kit
BECKETT
Beckett: A/C Ready Kit
Beckett: GeniSys® CAD Cell Flame Detector Kit | 7006U
BECKETT
Beckett: GeniSys® CAD Cell Flame Detector Kit | 7006U
Beckett: BeckettLink® Diagnostic and Configuration Tool | 7700A
BECKETT
Beckett: BeckettLink® Diagnostic and Configuration Tool | 7700A

Need a complete solution?

Product selection, system design, installation, and ongoing maintenance — all from one partner.